Florida (FBC 8th Ed. / 2023 FBC-R) requires specific deck prep before dry-in. Do not skip these steps.
- Re-nail the Deck (FBC-R §R905.2.1 / FBC-B §1507.2.1): 8d ring-shank nails @ 6" o.c. on all panel edges and 12" o.c. in the field (intermediate supports). This applies to all existing decks (plywood/OSB) in the High-Velocity Hurricane Zone (HVHZ: Miami-Dade/Broward) and Statewide for asphalt shingles per FBC-R §R905.2.1. Pro tip:* Use a palm nailer or gun. Missed nails = failed inspection.
- Inspect & Replace Damaged Sheathing (FBC-R §R905.1 / §R803): Replace any panel with delamination, rot, swelling, or deflection > 1/8". Gaps between panels > 1/8" must be filled or panel replaced (FBC-R §R803.2.2). Minimum 15/32" (1/2" nom.)* thickness for 24" truss spacing (FBC-R Table R503.2.1.1(1)).
- Tape Seams (HVHZ Only - FBC-B §1518.2 / FBC-R §R905.2.8.2): Miami-Dade & Broward ONLY: Apply 4" min. self-adhering polymer-modified bitumen tape over all plywood/OSB joints before* underlayment. This is your secondary water barrier (SWB).
- Clean & Dry (FBC-R §R905.1): Sweep debris. Deck must be dry* (moisture < 19% per NRCA) before underlayment. No puddles, dust, or protruding nails.
- Drip Edge (FBC-R §R905.2.8.1): Install metal drip edge* at eaves (under underlayment) and rakes (over underlayment). Overlap 2". Fasten 12" o.c.
Inspection Sequence: You must call for "Sheathing/Deck Nailing" inspection (or "Tin Tag" in some jurisdictions) before covering with underlayment. Building official verifies nail pattern, panel condition, and seam tape (HVHZ).
Licensed Pro Required? Deck replacement (structural) requires a licensed Roofing or General/Building Contractor in FL (F.S. 489.105). Simple re-nailing/prep can be done by the roofing crew.