It is a prohibited fitting orientation. A sanitary tee (san-tee) cannot be installed on its back (horizontal-to-horizontal) for drainage. It creates a 90° directional change without the required sweep radius, causing blockages and violating the fundamental "no 90s on the horizontal" rule.
Code Violation (IPC 706.3 / UPC 706.0):
- Sanitary Tees: Permitted only for vertical-to-horizontal (branch to stack) or vertical-to-vertical connections.
- Horizontal-to-Horizontal: Requires a Wye (Y) or Combination Wye & 1/8 Bend (Long Turn). A 4x3 Wye or 4x3 Combo is the correct fitting here.
Why "It fit" is wrong: A san-tee on its back has a sharp 90° interior corner. Solids stall there. A Wye directs flow at 45°; a Combo adds a long-radius sweep.
The Fix (Do this today):
- Cut out the san-tee and the short piece of 3" pipe connected to it.
- Install a 4x3 Wye (or Combo) on the 4" drain. Ensure the branch inlet is at 45° (not rolled up).
- Reconnect the 3" branch using a 45° ell if needed to align, maintaining 1/4" per foot fall.
- Support the new fittings per code (typically every 4 ft for 3"/4" PVC/ABS).
If the 3" branch is a vent: A san-tee on its back is also wrong for a dry vent takeoff (requires Wye or 45°). If it's a wet vent, same fix applies.
Bottom line: Inspector will red-tag this. Replace with a 4x3 Wye (or Combo) now.