No. A 3-inch building drain at 1/8 in/ft slope is not permitted for this load.
DFU Calculation (IPC Table 709.1 / UPC Table 702.1):
- 2 × Water Closets (1.6 gpf) @ 3 DFU = 6 DFU
- 2 × Lavatories @ 1 DFU = 2 DFU
- 2 × Bathtubs @ 2 DFU = 4 DFU
- Kitchen Sink w/ Disposer @ 2 DFU = 2 DFU
- Dishwasher (discharges to sink tailpiece) = 0 DFU (included in sink)
- Clothes Washer Standpipe @ 2 DFU = 2 DFU
- Total = 16 DFU
Code Capacity Check:
- IPC Table 710.1(1): 3-inch pipe at 1/8 in/ft slope → Max 14 DFU. (At 1/4 in/ft → 35 DFU).
- UPC Table 703.2: 3-inch pipe at 1/8 in/ft slope → Max 12 DFU (Horizontal). (At 1/4 in/ft → 35 DFU).
Result: Your 16 DFU exceeds the 14 DFU (IPC) or 12 DFU (UPC) limit for 3-inch at 1/8 in/ft.
Solutions:
- Increase slope to 1/4 in/ft (Capacity jumps to 35 DFU).
- Upsize to 4-inch pipe at 1/8 in/ft (IPC: 216 DFU; UPC: 180 DFU).
- Verify actual slope: If the installed pitch is steeper than 1/8 in/ft (e.g., 3/16 in/ft), interpolate capacity per code footnotes, but 1/4 in/ft is the standard fix.