Air Space (Cavity): 1" minimum (IRC R703.8.4 / TMS 402). Keep it clear of mortar droppings—use a mortar net or mesh at the base. This is your drainage plane; if it bridges, water reaches the sheathing.
Wall Ties (Anchors):
- Type: Corrosion-resistant (hot-dip galvanized or stainless steel). For coastal/Severe Weathering zones, stainless steel (Type 304/316) is required (IRC R703.8.4.1).
- Spacing: Max 24" horizontal x 16" vertical (IRC Table R703.8.4(1)). Within 12" of openings (windows, doors, corners) and top/bottom of walls.
- Embedment: Min 1.5" into mortar joint (bed joint preferred). Min 5/8" penetration into stud (not just sheathing). Screw into studs; nails withdraw.
- Veneer Weight: Standard brick veneer ≤ 40 psf. Heavier stone requires engineered spacing.
Weep Holes:
- Location: Immediately above flashing at base of wall, above lintels, above shelf angles, and at window/door heads.
- Spacing: Max 33" o.c. (IRC R703.8.6). 24" o.c. is better practice.
- Method: Open head joints (no mortar), plastic tubes, cotton wicks, or mesh vents. Open head joints are most reliable; tubes clog.
- Flashing: Critical. Through-wall flashing (metal or peel-and-stick) must lap over the WRB (housewrap) at base and under WRB at heads/sills. End dams at openings.
WRB: Two layers of Grade D paper or equivalent (IRC R703.2) over sheathing before lath/ties. Lap shingle-style.
Pro Tip: Install ties as you lay brick—don't pre-nail them all. Keeps alignment honest. Verify stud locations first.