Heat pump air handler with a 10 kW strip kit (nameplate says 41 A heater, MCA 52, MOP 60 for the combined unit).

Prompt as given to every model

Heat pump air handler with a 10 kW strip kit (nameplate says 41 A heater, MCA 52, MOP 60 for the combined unit). Installer brought #8 NM-B on a 50 A breaker because 'the heater is 41 amps.' Also landed the blower and strips on that one circuit. What's the problem?

Model answers

Pick up to two to compare side by side. Score chips fill in as the judge grades.

Nemotron 3 Ultra 550BScore —

Three code violations on one circuit:

  1. Conductor Ampacity (310.16 / 334.80): #8 NM-B (Romex) is limited to the 60°C column (334.80). Ampacity = 40 A. You cannot use the 75°C column (50 A) for NM-B. A 50 A breaker on 40 A wire is a fire hazard.
  2. Breaker Sizing / MCA (440.4(B), 110.3(B)): Nameplate MCA = 52 A. 440.4(B) requires branch circuit conductors and OCPD ≥ MCA. A 50 A breaker violates the listing.
  3. MOP Violation (440.22): Nameplate MOP = 60 A. While a 50 A breaker is under the MOP, it fails the MCA requirement above. The correct OCPD is 60 A.

The Fix:

  • Wire: Pull #6 NM-B (55 A @ 60°C) or #6 THHN in conduit (65 A @ 75°C).
  • Breaker: Install a 60 A 2-pole breaker.
  • Lugs: Verify air handler terminals accept #6 CU (most 60 A units do).

Note on "One Circuit": Landing blower + strips on a single circuit is standard for "single circuit entry" kits if the nameplate gives a single MCA/MOP (which yours does). No separate blower circuit needed.

Bottom line: Installer used wire rated 40 A on a 50 A breaker for a load requiring 52 A minimum. Re-pull with #6 CU and a 60 A breaker.

543 tokens · 21.3s

Judge rubric · pending

Not graded yet. Grading starts when the exam run completes.

Nemotron 3 Super 120BScore —

The installer’s approach violates NEC requirements for continuous loads and equipment rating.

Problem: The 10 kW strip heater draws 41 A, but per NEC 424.3(B), fixed electric space-heating equipment is considered a continuous load (operating 3+ hours). Continuous loads require conductors and overcurrent protection rated at 125% of the load.

  • 41 A × 1.25 = 51.25 A minimum for both conductor and breaker.
  • Nameplate MCA (Minimum Circuit Ampacity) is 52 A, confirming the unit requires ≥52 A circuit capacity.
  • MOP (Maximum Overcurrent Protection) is 60 A, meaning the breaker must not exceed 60 A.

What was done wrong:

  • Using #8 NM-B (rated 40 A at 60°C per Table 310.16) on a 50 A breaker is invalid:
  • #8 NM-B is limited to 40 A (60°C column) — undersized for 52 A MCA.
  • Even if using 75°C terminals, #8 Cu is 50 A (75°C column) — still below 52 A MCA.
  • Landing both blower and strips on one circuit is acceptable only if the circuit meets MCA/MOP — but it doesn’t.

Correct fix:

  • Use #6 AWG Cu NM-B (rated 55 A at 60°C, 65 A at 75°C) — satisfies 52 A MCA.
  • Protect with a 50 A or 60 A breaker (MOP allows up to 60 A; 50 A is acceptable if it doesn’t trip on startup, but 60 A is common for heat pumps).
  • Verify blower amps are included in the nameplate MCA (they should be — MCA already accounts for all loads).

Bottom line: The circuit is undersized and overprotected relative to conductor rating. Replace with #6 Cu and a 50–60 A breaker per unit nameplate and NEC 424, 440, and 310.16. If unsure, consult a licensed electrician — incorrect sizing risks overheating and fire. (Word count: 248)