Hunting causes & fixes:
- Sensing bulb mounting (most common issue): - Must be mounted 30° above horizontal on the suction line, 12-18" from the evaporator outlet - Use proper insulation over the bulb and 12" of line upstream/downstream - Bulb must be snug against the line with no air gap - use a thermal paste or aluminum tape - No insulation between bulb and line
- Check these areas: - Refrigerant charge - verify with superheat/subcooling (not just pressures) - TXV powerhead - ensure proper torque on the bulb (typically 15-20 inch-lbs) - Evaporator airflow - check for dirty coils, duct issues, or blower problems - Liquid line - ensure adequate subcooling (8-12°F typical) and no restrictions
- System issues: - Oversized TXV for the application - Internal valve problems - check for debris or worn components - Pressure drops in the liquid line
Quick test: If you bypass the TXV temporarily and superheat stabilizes, the valve is likely faulty.
Code reference: Follow ACC A10-2015 for proper refrigerant system installation practices.
If the bulb is properly mounted and charged correctly but still hunting, the TXV itself may need replacement.