Heat pump customer thinks the unit is broken because it 'blows cold' and 'steams' for a few minutes on a cold morning.

Prompt as given to every model

Heat pump customer thinks the unit is broken because it 'blows cold' and 'steams' for a few minutes on a cold morning. Explain what's actually happening and when it's a real problem.

Model answers

Pick up to two to compare side by side. Score chips fill in as the judge grades.

Laguna S 2.1Score —

What's Actually Happening:

On cold mornings, your heat pump enters defrost mode — this is normal operation, not a malfunction. Here's the process:

  1. Ice builds up on the outdoor coil during heating operation (especially when ambient temps drop below 40°F).
  2. The system automatically switches to defrost mode — temporarily reversing into air conditioning mode.
  3. The outdoor coil gets hot, melting the ice. You'll see steam (water vapor) rising from the unit — this is normal.
  4. The indoor air may feel cooler for 5-15 minutes during this cycle.

When It's a Real Problem:

  • Steam lasts more than 30 minutes — indicates a defrost control issue
  • No steam but ice buildup visible — defrost cycle isn't activating
  • Unit runs constantly in cold weather without adequate heating
  • Ice thicker than 1/4 inch that doesn't clear during defrost
  • Cold air for more than 20 minutes continuously

Code Reference: Per ACC ASHRAE 90.1-2019 Section 6.4.1, heat pumps must have automatic defrost controls. The steaming is the system working correctly.

Bottom Line: Brief steaming and cooler air for 5-15 minutes on cold mornings is normal defrost operation. If it persists beyond 30 minutes or you see excessive ice buildup, call a technician.

420 tokens · 9.7s

Judge rubric · pending

Not graded yet. Grading starts when the exam run completes.

Nemotron 3 Ultra 550BScore —

What's Happening: Normal Defrost Cycle On cold mornings (typically below 40°F), moisture freezes on the outdoor coil. The system must melt this ice to maintain efficiency. It does this by temporarily reversing into cooling mode (hot gas goes to outdoor coil).

What the Customer Experiences:

  1. "Blows Cold Air": The indoor coil becomes the evaporator (cold). Auxiliary heat (strip heat) should energize simultaneously to temper this air. If strips are undersized, broken, or not wired to run during defrost, the supply air feels cold.
  2. "Steams/Smokes": The outdoor unit fan stops; hot refrigerant melts ice rapidly. The resulting water vapor looks like white smoke/steam rising from the unit. This lasts 2–10 minutes.

When It’s a Real Problem (Requires Service):

  • Supply air stays cold >15 min after defrost ends: Defrost termination sensor/control board failure (stuck in defrost).
  • No steam, but unit iced solid: Defrost not initiating (bad sensor, board, or reversing valve).
  • Frequent defrosts (<35 min apart) with light frost: Bad outdoor thermistor/thermostat or low charge.
  • Aux heat never kicks on during defrost: Check wiring at air handler (W2/E terminal) and strip heat sequencers/breakers. NEC 424.3(B) requires overcurrent protection for strips.
  • Loud "clanking" during reversal: Failing reversing valve solenoid or compressor valves.

Action Items for You:

  1. Verify auxiliary heat energizes during defrost (check W2 voltage at air handler).
  2. Confirm defrost termination temperature (usually 55–70°F coil temp).
  3. Check refrigerant charge (low charge = excessive frost/short cycling).
  4. Educate the customer: This is the machine working to protect the compressor.
541 tokens · 3.4s