Charging a TXV System: Targets & Measurement Points
With a TXV (Thermostatic Expansion Valve), charging is based on superheat and subcooling, not fixed pressures.
Charging Target:
- Subcooling: Typically 10–15°F (varies by manufacturer; check nameplate or specs).
- Superheat: Should match the rated superheat listed on the TXV or manufacturer data (usually 8–12°F).
Where to Take Readings:
- Suction Line (Low Side): - Temperature: Insulate and measure at the service valve or evaporator outlet. - Pressure: Connect gauge to suction service port. - Superheat = Suction Temp – Saturated Temp (from pressure).
- Liquid Line (High Side): - Temperature: Measure at the liquid line near the TXV inlet (after the filter/dryer). - Pressure: Connect gauge to liquid line service port or high-side gauge. - Subcooling = Saturated Temp (from pressure) – Liquid Line Temp.
Steps:
- Recover refrigerant if overcharged; add if undercharged.
- Adjust charge until: - Subcooling = 10–15°F - Superheat = 8–12°F (or per TXV specs)
- Verify stable superheat across load changes.
Notes:
- Ensure proper airflow across the condenser and evaporator.
- Use correct refrigerant type and oil compatibility.
- If readings are unstable, check for refrigerant restrictions, oversized TXV, or metering issues.
Safety: Always wear PPE and follow EPA 608 guidelines. If unsure, consult manufacturer specs or a licensed technician.