Apprentice roughed in an EV charger circuit: 6-2 NM-B from a 60A breaker, 45 feet through the attic, into a hardwired EVSE set to 48A.

Prompt as given to every model

Apprentice roughed in an EV charger circuit: 6-2 NM-B from a 60A breaker, 45 feet through the attic, into a hardwired EVSE set to 48A. Wire and breaker are both 'rated 60' per the label on the cable reel. Inspector wants it redone. Why?

Model answers

Pick up to two to compare side by side. Score chips fill in as the judge grades.

Laguna S 2.1Score —

NEC 625.47(A) requires EV charging circuits to have no other loads and be dedicated. Your 6-2 NM-B setup fails multiple code requirements:

  1. Ampacity (NEC 310.15(B)(16)): 6 AWG copper is rated 65A at 75°C, but NM-B is 90°C rated. However, 625.47(C) requires conductors to be sized for 125% of the continuous load. A 48A EVSE = 48 × 1.25 = 60A minimum. 6 AWG NM-B is only rated 55A at 60°C (NM-B's termination rating per 110.14(C)(1)(a)), which is undersized.
  1. Breaker Compatibility (NEC 240.4(D)): 6 AWG copper requires a 60A breaker max for NM-B (due to 110.14(C) 60°C limitation). A 60A breaker on 55A wire is a code violation.
  1. Hardwired EVSE (NEC 625.47(B)): Requires individual conductors in conduit or 6-2 NM-B with equipment grounding conductor (EGC). Your 6-2 NM-B lacks an EGC, which is mandatory for hardwired installations.

Fix: Replace with 6/3 NM-B (adding EGC) or run 6 AWG x 3 conductors in conduit with a 60A breaker. Alternatively, use 4 AWG NM-B (65A at 60°C) with a 60A breaker if the EVSE allows.

Safety Note: This requires a licensed electrician. The undersized wire and missing EGC create fire and shock hazards.

550 tokens · 13.0s

Judge rubric · pending

Not graded yet. Grading starts when the exam run completes.

Nemotron 3 Ultra 550BScore —

The inspector is correct. 6/2 NM-B is not rated for 60A. You have a fundamental ampacity mismatch.

The Code Violation (NEC 310.16 / 334.80):

  • 60°C Column (NM-B limit per 334.80): 6 AWG Copper = 55 Amps.
  • 75°C Column (Breaker terminal limit per 110.14(C)): 6 AWG Copper = 65 Amps.
  • Rule: You must use the lower of the two: 55 Amps max.

The Circuit Design Failure (NEC 210.19(A)(1), 625.41, 215.2(A)(1)(b)):

  1. Continuous Load: EV charging is a continuous load (3+ hours). Conductors and OCPD must be sized at 125% of load.
  2. Load Calculation: 48A (EVSE setting) × 1.25 = 60A minimum circuit ampacity required.
  3. OCPD Sizing: Breaker must be ≥ 60A (next standard size 625.42). A 60A breaker requires 60A conductor ampacity.
  4. The Conflict: Your wire maxes out at 55A. You cannot legally protect it with a 60A breaker (240.4(D) does not apply to #6; 240.4(B) "next size up" only applies if ampacity does not correspond to a standard breaker—55A does not, but 60A breaker exceeds the 55A conductor rating, violating 240.4(D) logic for small conductors and 110.14(C) thermal limits).

The Fix: You need 4/2 NM-B (or 4/3 if neutral required).

  • 4 AWG NM-B (60°C Column) = 70 Amps.
  • Supports the 60A breaker and 48A continuous load legally.
  • Check voltage drop: 45ft @ 48A on #4 Cu ≈ 1.8% (Well within 3% branch circuit recommendation).

Action: Pull the 6/2. Install 4/2 NM-B. Keep the 60A breaker. Re-inspect.