Inspector failed my panel because the water heater is too close in front of it.

Prompt as given to every model

Inspector failed my panel because the water heater is too close in front of it. What are the actual clearance numbers?

Model answers

Pick up to two to compare side by side. Score chips fill in as the judge grades.

Laguna S 2.1Score —

NEC 2023, Section 110.26(A) requires a minimum 3-foot (36") clearance in front of all electrical equipment (including panels) for safe access and working space. This is the key requirement your inspector cited.

Additional clearances:

  • 110.26(A)(1): 30" wide minimum working space (measured from the panel door to the nearest obstruction).
  • 110.26(A)(2): 36" minimum depth (front-to-back) for working space.
  • 110.26(A)(3): 30" width of working space (can be less if the panel is narrower).

For your water heater:

  • The 36" front clearance is the critical issue. If the water heater is within 36" of the panel door, it violates this rule.
  • If the water heater is adjacent to the panel (not directly in front), ensure the 30" width and 36" depth requirements are met.

Solutions:

  1. Relocate the water heater to maintain 36" clearance in front of the panel.
  2. Install a barrier or shield if the water heater is adjacent (check local codes for approval).
  3. Verify the panel door opens fully without obstruction.

Note: Local amendments may apply. If unsure, consult a licensed electrician or inspector for confirmation. The 36" front clearance is non-negotiable under NEC 110.26(A).

411 tokens · 6.5s

Judge rubric · pending

Not graded yet. Grading starts when the exam run completes.

Nemotron 3 Ultra 550BScore —

NEC 110.26(A) Working Space Requirements:

Depth (in front of panel):

  • 36 inches minimum for 0–150V to ground (residential 120/240V)
  • 42 inches for 151–600V to ground

Width:

  • 30 inches minimum (or panel width, whichever is greater)
  • Centered on panel

Height:

  • 6.5 feet (78 inches) minimum headroom from floor/grade

Critical for your situation: The water heater cannot encroach into this 36"×30"×78" dedicated space. It's not "equipment" allowed in the working space — it's a separate appliance.

Common fixes:

  1. Relocate water heater (only compliant option if space is tight)
  2. Relocate panel (if heater stays)
  3. Build a code-compliant enclosure around heater only if it maintains all clearances and doesn't create a new hazard (rarely practical)

NEC 110.26(E) explicitly prohibits using working space for storage. A water heater is permanent equipment, not storage — same violation.

Measure from: Panel face (dead front) outward. Not from wall, not from breaker handles.

If you're at 30" depth: You're 6" short. Inspector is correct. No exceptions for "it's always been there" or "it's a small heater."

Licensed electrician required for panel relocation. Plumber for heater move.