Customer bought a Level 2 EV charger that can be set to 48 amps and wants it hardwired in the garage, 30 feet from the panel.

Prompt as given to every model

Customer bought a Level 2 EV charger that can be set to 48 amps and wants it hardwired in the garage, 30 feet from the panel. What breaker and wire?

Model answers

Pick up to two to compare side by side. Score chips fill in as the judge grades.

Laguna S 2.1Score —

For a 48A EV charger hardwired 30 feet from the panel:

Breaker: 60A 2-pole (NEC 625.41 requires the branch circuit rating to match the charger's maximum current setting; 48A × 1.25 = 60A).

Wire: 6 AWG copper THWN-2 (minimum 60A ampacity per 310.16 at 75°C) or 4 AWG aluminum XHH-2. Use 10 AWG copper or 8 AWG aluminum for the equipment grounding conductor (250.122).

Cable assembly: 3 conductors + ground (2 hots, 1 neutral if the charger requires 120V control power—check specs; many 240V-only units don't need a neutral).

Installation notes:

  • Use a dedicated circuit (625.41).
  • Conduit or armored cable (e.g., ¾" EMT or 1" PVC) for physical protection.
  • Hardwired connection per manufacturer's instructions; no receptacle allowed for hardwired units (406.88).
  • GFCI protection may be required depending on local code amendments—check with AHJ.
  • Torque connections per 110.14(D) using manufacturer's specifications.

Safety: This is electrical work requiring proper licensing in most jurisdictions. If you're not a licensed electrician, hire one—this involves high-amperage 240V circuits that can cause serious injury or fire if installed incorrectly.

443 tokens · 6.9s

Judge rubric · pending

Not graded yet. Grading starts when the exam run completes.

Nemotron 3 Ultra 550BScore —

Breaker: 60A 2-pole Wire: 6 AWG THHN/THWN-2 in conduit (or 6/3 NM-B if concealed and protected)

Code Basis (2023 NEC):

  • 625.41(A): EVSE is a continuous load → breaker = 125% of nameplate. 48A × 1.25 = 60A.
  • 625.42: Branch circuit ampacity ≥ nameplate (48A). 6 AWG copper = 55A (75°C column, Table 310.16) — but 625.41(A) requires 125% for OCPD, not conductor. Conductor must carry 48A continuous → 6 AWG (55A @ 75°C) is sufficient per 210.19(A)(1)(a) Exception.
  • 310.14(C): 60A breaker protects 6 AWG (next standard size up per 240.4(B)).
  • 300.22 / 334.15: NM-B allowed in garage walls/ceilings if protected from physical damage. Otherwise, EMT/PVC with THHN.
  • 625.54: GFCI protection required (breaker or device). Most 48A units have built-in; verify. If not, use 60A 2-pole GFCI breaker.
  • 625.43: Disconnect required within sight or lockable. Hardwired unit with lockable breaker satisfies.

Installation Notes:

  • 30 ft run: voltage drop ~2.5% at 48A (6 AWG) — acceptable.
  • Torque lugs to spec. Label circuit “EVSE – 48A Continuous.”
  • Permit and inspection required.

If aluminum wire: Use 4 AWG Al (65A @ 75°C). Not recommended for short runs.

Bottom line: 60A breaker, 6 AWG Cu, GFCI-protected, permitted.