Yes, a 20A breaker with #12 AWG copper wire is acceptable for this installation, but with important caveats.
Code Compliance:
- NEC 210.20(A) requires overcurrent protection to not exceed the ampacity of conductors. #12 copper is rated 20A (90°C column, NEC Table 310.16), matching the breaker.
- NEC 210.19(A)(1) requires conductors to have ampacity not less than the load. Your 18A load is within the 20A capacity.
- NEC 210.23(A) allows 20A loads on 20A branch circuits.
Critical Considerations:
- Continuous Load: If these lights operate for 3+ hours continuously (likely for "all night"), NEC 210.20(A) requires sizing the breaker at 125% of the load. 18A × 1.25 = 22.5A, which exceeds a 20A breaker. You'd need a 25A breaker with #10 AWG wire, or verify the load is actually under 16A continuous (16A × 1.25 = 20A).
- Voltage Drop: For runs over 50 feet, check voltage drop. NEC 210.19(A)(1) Informational Note recommends ≤3% drop. At 18A, #12 may cause noticeable dimming on long runs.
Recommendation:
- If the load is truly 18A non-continuous, your setup works.
- If continuous, either reduce load below 16A or upgrade to 25A breaker with #10 AWG wire.
- Consider having an electrician verify the actual continuous load and wire length.
Safety Note: Churches often have insurance requirements exceeding minimum code. Check with your insurer and local AHJ, as some jurisdictions require permits for new circuits.