I'm pulling four 20A 120V circuits through one 3/4 EMT from a panel to a shop, each circuit with its own neutral, plus one ground, THHN.

Prompt as given to every model

I'm pulling four 20A 120V circuits through one 3/4 EMT from a panel to a shop, each circuit with its own neutral, plus one ground, THHN. Do I need to upsize the wire?

Model answers

Pick up to two to compare side by side. Score chips fill in as the judge grades.

Laguna S 2.1Score —

No, you do not need to upsize the wire.

Here's why:

Conduit Fill Calculation:

  • 4 circuits × (1 hot + 1 neutral) = 8 current-carrying conductors
  • 1 equipment grounding conductor (EGC)
  • Total: 9 conductors in 3/4" EMT

Fill Check (NEC Chapter 9, Table 1 & Table 4):

  • 3/4" EMT = 0.622 sq in. usable area
  • 9 conductors × 0.0133 sq in. (for 12 AWG THHN) = 0.1197 sq in.
  • Fill percentage: 0.1197 ÷ 0.622 = 19.2% (well under the 53% max for 3+ conductors)

Ampacity Adjustment (NEC 310.15(B)(3)(a)):

  • 8 current-carrying conductors (CCCs) require derating
  • 12 AWG THHN derated at 70% (Table 310.15(B)(3)(a)) = 17.5A
  • Since 17.5A > 15A (the circuit's OCPD for a 20A breaker with 12 AWG), no adjustment needed

Conclusion: Your 3/4" EMT with 12 AWG THHN is compliant. The conduit fill is acceptable, and the ampacity adjustment doesn't require upsizing.

Note: Ensure the 20A breakers are rated for 12 AWG wire (they should be). If you were using 15A breakers, you'd need to upsize to 14 AWG.

500 tokens · 14.2s

Judge rubric · pending

Not graded yet. Grading starts when the exam run completes.

Nemotron 3 Ultra 550BScore —

No upsizing required for ampacity, but you have a fill problem.

Ampacity (310.16 / 310.15(B)(3)(a)):

  • 9 THHN current-carrying conductors (4 hots + 4 neutrals + 1 spare? No, you listed 4 hots, 4 neutrals, 1 ground = 9 total, 8 CCC).
  • 8 CCC requires 70% adjustment factor.
  • #12 THHN (90°C col) = 30A × 0.70 = 21A.
  • 20A breaker protects #12 per 240.4(D)(5). Pass.

Conduit Fill (Chapter 9, Table 1, Table 4, Table 5):

  • 3/4" EMT 40% fill limit = 0.213 in².
  • #12 THHN area (Table 5) = 0.0133 in².
  • 9 wires × 0.0133 = 0.1197 in².
  • Wait. You have 4 hots + 4 neutrals + 1 ground = 9 wires.
  • 9 × 0.0133 = 0.1197 in². This is < 0.213 in². Fill is OK.

Correction: My initial mental math was wrong. 9x #12 fits easily in 3/4" EMT (40% fill = ~16 wires max).

The Real Issue: Multiwire Branch Circuits (210.4) Since you are pulling 4 circuits with dedicated neutrals, you have 4 separate MWBCs (or 4 individual circuits).

  • Handle Ties Required (210.4(B)): Each pair sharing a neutral (or in this case, each circuit's hot/neutral pair if treated as MWBC) needs a common trip. Since neutrals are separate, they are technically individual circuits, not MWBCs. No handle ties needed.
  • Neutral Identification (200.4): Each neutral must be identified (white/gray) per circuit. Use colored tape/stripes at both ends.

Grounding (250.122 / 300.3(B)):

  • One #12 ground serves all 4 circuits (sized for largest OCPD, 20A).
  • Ground counts for fill, not ampacity adjustment.

Verdict: #12 THHN is Code-compliant for ampacity and fill. Pull away. Label neutrals clearly.