No, you do not need to upsize the wire.
Here's why:
Conduit Fill Calculation:
- 4 circuits × (1 hot + 1 neutral) = 8 current-carrying conductors
- 1 equipment grounding conductor (EGC)
- Total: 9 conductors in 3/4" EMT
Fill Check (NEC Chapter 9, Table 1 & Table 4):
- 3/4" EMT = 0.622 sq in. usable area
- 9 conductors × 0.0133 sq in. (for 12 AWG THHN) = 0.1197 sq in.
- Fill percentage: 0.1197 ÷ 0.622 = 19.2% (well under the 53% max for 3+ conductors)
Ampacity Adjustment (NEC 310.15(B)(3)(a)):
- 8 current-carrying conductors (CCCs) require derating
- 12 AWG THHN derated at 70% (Table 310.15(B)(3)(a)) = 17.5A
- Since 17.5A > 15A (the circuit's OCPD for a 20A breaker with 12 AWG), no adjustment needed
Conclusion: Your 3/4" EMT with 12 AWG THHN is compliant. The conduit fill is acceptable, and the ampacity adjustment doesn't require upsizing.
Note: Ensure the 20A breakers are rated for 12 AWG wire (they should be). If you were using 15A breakers, you'd need to upsize to 14 AWG.