Do NOT bond the neutral bar in the subpanel.
In a subpanel, the neutral and ground bars must be isolated from each other and from the enclosure. This is required by NEC 250.142(B) and 250.32(B)(1).
Why:
- The main panel is the only point where neutral and ground should be bonded (NEC 250.24(C)).
- If you bond them again in the subpanel, it creates a parallel path for neutral current on the grounding conductors and enclosure, which can cause:
- Overheating
- Electric shock risk
- Improper operation of breakers
What to do:
- Remove the bonding strap or screw connecting the neutral bar to the enclosure in the subpanel.
- Ensure the neutral bar is mounted on insulated standoffs (not touching the metal box).
- Run a separate equipment grounding conductor (EGC) with your feeder cables (NEC 250.32(B)(1)).
- Use a 4-wire feeder: two hots, one neutral, one ground (NEC 250.32).
Exception: If you're using a metal raceway (like EMT) that's properly bonded, it can serve as the EGC, but you still must not bond neutral to the subpanel enclosure.
Since this is in the same building and under 20 feet, you don't need a separate disconnect at the subpanel unless local code requires it.
Bottom line: No neutral-to-enclosure bonding in the subpanel. Keep neutral and ground separate.