Megger Test Procedure (480V Feeder):
- Safety First: Lock out and tag out the breaker. Verify no voltage with a multimeter before connecting the megger.
- Isolate the Circuit: Disconnect power at both ends. Remove wires from terminals to avoid testing through connected loads or devices.
- Test Setup: - Use a 1000V DC megger (standard for 480V systems). - Test each conductor to ground (phase-to-ground) and phase-to-phase. - Connect one lead to the conductor, the other to a good ground or adjacent conductor.
- Environmental Conditions: - Test when the conduit/wires are dry. Moisture will skew results. If still damp from rain, wait or use temporary heat (fan) to dry.
- Acceptable Readings: - >10 MΩ = Good (per NEC MAINTENANCE guidelines). - 1–10 MΩ = Marginal; monitor or retest when dry. - <1 MΩ = Conductor has leakage/failure; likely damaged by water.
- Interpretation: - Low readings after rain = water ingress, likely through conduit seals, damaged insulation, or improper routing. - Consistent low readings across all phases = common issue (e.g., shared conduit problem).
Conclusion: If readings are below 10 MΩ, especially after drying, plan to replace the wire. Also inspect conduit routing and seals to prevent future issues.
Let me know if you need help interpreting specific readings.