Inspection outcome: The inspector will most likely fail the dry-in.
Code violations (per IRC/Florida Building Code – Residential, 2020 ed.):
- Roof decking fasteners (Section R803.2 / R502.3): - 7/16" OSB requires 8d common nails (0.162" shank, 2½" long) — OK. - Spacing must be 6" o.c. at edges and 12" o.c. in the field — OK. - However, smooth-shank nails are not compliant in high-wind zones. Code requires ring-shank or screw nails for 7/16" OSB in 130 mph zones (per manufacturer specs and FBC Section R502.3.1). - Fix: Replace with 8d ring-shank nails** or #8 screws at 6"/12" spacing.
- H2.5 clips (Section R802.3 / R502.3.1): - Must be installed on every truss — not every other one. - Each clip requires three 8d x 1½" (or 1¼") common nails — OK if used. - Fix: Install H2.5 clips on every truss, properly fastened.
Bottom line: The inspector will flag both the nail type and missing clips. You’ll need to remove and replace smooth nails with ring-shank and add clips to every truss before re-inspection.
Safety note: This is a structural/wind uplift issue — improper fastening can lead to roof failure in storms. Not a DIY fix if you're not experienced with roofing systems.