STOP — DO NOT PASS INSPECTION AS-IS.
Cutting bottom chords and webs of trusses is a structural modification that requires engineering approval. Trusses are designed as integrated systems; removing members without analysis violates IRC Section R802.3 and IBC Section 2308, which require truss alterations to be designed by a registered engineer or pre-approved by the truss manufacturer.
Immediate actions:
- Halt the sistering plan. Nailing 2x6s alongside cut chords does NOT restore truss capacity. Truss members are sized for specific loads in compression/tension — field repairs need calculated connection details and material matching.
- Call a structural engineer to design a proper repair (likely steel plates, splice connections, or temporary shoring).
- Notify the inspector that the work is incomplete and awaiting engineered plans. Do not attempt to pass inspection with an unapproved repair.
- Contact the truss manufacturer — they may provide a field repair detail if the cut is within their repair policy.
Safety risk: Attic loading, wind uplift, or snow loads could cause failure. Trusses are not like rafters — field modifications are not allowed without engineering.
Bottom line: Tell the contractor the framer’s fix is inadequate and unsafe. Get an engineer involved before inspection. If none available, reschedule and remove the unit temporarily.
Cite: IRC R802.3.1, IBC 2308.9, and truss design standards (TPI 1).